Signal conditioner – Ultra SlimPak II

 

Signal conditioner

The signal conditioner Ultra SlimPak II is an exciting new line of signal conditioners from Action Instruments with greater accuracy and better stability, it features Smart Power, which eliminates wasted power for low loop resistance loads in the current output mode.

These signal conditioners can function as traditional standalone limit alarms and isolators, or they can simultaneously be connected to your company’s intranet to monitor your signals via a standard browser when coupled with the optional WVC16 interface unit.

Description

Click to rate this post!
[Total: 0 Average: 0]
  • Ethernet Connectivity to Most Client Software
  • Built In Web Browser with Email and Logging Capability
  • PC or Button Setup and Calibration
  • Smart Power Technology Automatically Adjusts Power
  • High Density Modules
  • Reduced Wiring with Jumpers Transferring Power from
  • Module to Module
  • Removable Connectors
  • Fast Response and High Accuracy
  • In-Process Calibration
Ordering Information
Part number Function Input Input Span (Field Configurable) Housing Width Output (Field Configurable

WV408

Isolator DC Volts +/-150mV, +/-1.5V, +/-15V, +/-150V 12.7mm DC Voltage (0-10V)
DC Current +/-2.5mA, +/-25mA DC Current (0-20mA, 4-20mA)
(95%adjustment in any range)

WV108

Limit Alarm DC Volts +/-20mV, +/-200mV, +/-2V, +/-20V, +/-200V 17.5mm Alarm (Dual SPDT Relay)
DC Current +/-10mA, +/-100mA

WV418

Isolator 2, 3 & 4 Wire RTD Platinum RTD: -200 to 600°C 17.5mm DC Voltage (0-10V)
Copper RTD: -200 to 260°C DC Current (0-20mA, 4-20mA)
(95%adjustment in any range) (95%adjustment in any range)

WV118

Limit Alarm 2 & 3 Wire RTD Platinum RTD: -200 to 600°C 17.5mm Alarm (Dual SPDT Relay)
Copper RTD: -200 to 260°C
(95%adjustment in any range)

WV428

Isolator Thermocouple Type B: 75 to 1800°C 12.7mm DC Voltage (0-10V)
Type C: 0 to 2315°C (428 only) DC Current (0-20mA, 4-20mA)
Type E: -200 to 1000°C (95%adjustment in any range)
Type J: -210 to 760°C
Type K: -200 to 1370°C
Type N: -200 to 1300°C (428 only)
Type R/S: 0 to 1760°C
Type T: -200 to 390°C
(95%adjustment in any range)

WV128

Limit Alarm Thermocouple Type B: 75 to 1800°C 17.5mm Alarm (Dual SPDT Relay)
Type C: 0 to 2315°C (428 only)
Type E: -200 to 1000°C
Type J: -210 to 760°C
Type K: -200 to 1370°C
Type N: -200 to 1300°C (428 only)
Type R/S: 0 to 1760°C
Type T: -200 to 390°C
(95%adjustment in any range)

WV438

Isolator Potentiometer 100 ohms to 100k ohms 12.7mm DC Voltage (0-10V)
DC Current (0-20mA, 4-20mA)
(95%adjustment in any range)

WV448

Isolator Strain Gauge +/-5mV to +/-200mV 17.5mm DC Voltage (0-10V)
Excitation: 1-10VDC @ 120mA DC Current (0-20mA, 4-20mA)
(95%adjustment in any range)

WV468

Isolator AC Volts 50mV AC to 250VAC 12.7mm DC Voltage (0-10V)
AC Current 20mA AC to 100mA AC DC Current (0-20mA, 4-20mA)
(95%adjustment in any range)

WV168

Limit Alarm AC Volts 50mV AC to 250VAC 17.5mm Alarm (Dual SPDT Relay)
AC Current 20mA AC to 100mA AC

WV478

Isolator Frequency 2Hz to 10kHz 12.7mm DC Voltage (0-10V)
DC Current (0-20mA, 4-20mA)
(95%adjustment in any range)

WV905

Power Supply AC Power 85 to 265VAC, 50 to 60Hz 22.5mm 24VDC @ 500mA
DC Power 120 to 300VDC

WVC16

Communications Interface DC Power 22.5mm Config summary/editing; diagnostics; alarm setup/
/ status; e-mail; process variable viewing; data logging

Documentation